Elettra Multichannel Lamp — Modbus RTU Configurator

Drives and configures Elettra multichannel lamps over Modbus RTU directly from the browser, via Web Serial: channel intensities and master dimmer, power-on state, zones, slave ID and serial settings, ID assignment by MAC address on a bus of identical lamps, and the reboot / web-server commands.

All registers are 16-bit holding registers with 0-based addresses, read with function 0x03 and written with 0x06 / 0x10. Writes to slave address 0 are broadcasts: every lamp executes them and none replies.

Web Serial API not available in this browser. Use a Chromium-based browser (Chrome, Edge, Opera) on desktop.

1. Connection

DISCONNECTED
Factory defaults: ID 1, 9600 baud, 8N1, zone 0. Lamps fresh from the factory all share ID 1: on a bus with several of them, unicast reads collide, so only broadcast writes work until each lamp gets its own ID (section 5). The slave ID can be changed at any time without reconnecting.
Find lamps on the bus
Reads the firmware version register (100) from each ID with a short timeout. Click a found ID to select it. A reply with a CRC error usually means two or more lamps share that ID.

2. Lamp Status

Outputs (1000)
—
Master (1001)
—
Thermal limit (1018)
—
ChannelRegSettingEffective output
Effective output = channel × master × thermal limit, and 0 when the outputs are disabled. The thermal limit reads 100% in normal conditions; anything lower means the lamp is derating because it is overheating, which the manufacturer treats as a fault condition worth reporting to support.

3. Channel Control

Same channel on several lamps

Sets one channel on each listed lamp and leaves its other channels, master and output enable as they are. The lamp only takes 2000–2017 as a block, so for each ID the tool reads the active state (1000–1017), changes the chosen channel and writes 2000–2018 back to that ID. Lamps are handled one after the other; a lamp that fails is reported and the others still get the command. IDs are a comma-separated list of IDs or ranges (e.g. 1-4, 7, 10).

Power-on state

Apply writes registers 2000–2018 in a single function 0x10 frame; the lamp only takes the new values when register 2018 is written with bit 15 set, so all 19 registers always go together. 2018 carries 0x8000 + zone: zone 0 reaches every lamp, any other zone only the lamps configured for it (and lamps left in zone 0). All Lamps Off broadcasts output enable = 0 to zone 0 and leaves the channel values in place.
Save Current State (207 = 257) stores the active channel state as the power-on state, so the lamps can then be cycled on and off with a timer on their supply. Restore Saved State (207 = 258) reloads it. Both go to the target selected above.

4. Device Settings

Firmware (100)
—
Baud rate (200)
—
Frame (201)
—
Slave ID (202)
—
Zone (203)
—
Writes registers 200–203 with function 0x10, then 207 = 260, which saves them and reboots the lamp. The values only take effect after that reboot. If you change the baud rate or frame format, disconnect and reconnect with the new settings; the connection form is filled in for you.
Broadcasting to all lamps gives them all the same ID and zone: use it to change the bus speed of every lamp at once, and section 5 to give them distinct IDs.
Zone: 0 = accepts every zone command (default), 1–32767 = member of that zone, 32768–65535 = zone commands ignored.

5. Assign ID by MAC Address

204 = — · 205 = — · 206 = —
For a bus where several lamps still share the same ID. The MAC address is on the label of each lamp's control box. Assign broadcasts registers 204–206 (the MAC, byte-swapped in pairs) and then writes the new ID to 207: only the lamp whose MAC matches takes the ID. Verify reads register 202 from the new ID. The manual does not say whether the new ID is stored permanently; if the lamp loses it after a power cycle, run Save on Lamp (207 = 260 sent to the new ID). Repeat for each lamp.

6. Maintenance

Reboot writes 207 = 256. Start Web Server writes 207 = 259: the lamp opens a Wi-Fi access point named alGW-<MAC> (password 12345678); browse to 10.10.10.10 for the channel page or 10.10.10.10/update for firmware updates. It closes after 10 minutes and the lamp reboots. The web interface can interfere with Modbus control, so use it for diagnostics only.
Factory reset (button on the control board only)
Open the control box on top of the lamp (four screws). Do not unplug any cable or connector inside it.
  1. Hold the button for at least 5 s, until the three red LEDs light.
  2. Release and press again within 5 s; hold for at least 10 s, until the LEDs flash fast.
  3. Release and press again within 5 s; hold for at least 10 s, until the LEDs turn off.
  4. Release within 5 s. The LEDs cycle in sequence while the parameters reset, then the board reboots.

A short press makes the LEDs and channels blink: a quick check that the board is alive. The green LED must always be on; if it is off the control board has no power.

Register map
RegisterAccessContent
100RFirmware version (high byte . low byte)
200R/WBaud rate / 10 (default 960 = 9600)
201R/WFrame, 8 data bits: bits 0–1 stop bits (2 = two, else one); bits 2–3 parity (1 = even, 2 = odd, else none)
202R/WSlave ID 1–247 (default 1)
203R/WZone: 0 all, 1–32767 zone, 32768+ zone control off
204–206R/WMAC match for ID assignment by broadcast
207R/WCommand: 1–247 set ID if MAC matches · 256 reboot · 257 save channel state · 258 load channel state · 259 start web server · 260 save 200–203 and reboot
1000ROutputs enabled (0/1)
1001RMaster 0–32768
1002–1017RChannels 1–16, 0–32768
1018RThermal limit, 32768 = none
2000R/WSet outputs enabled
2001R/WSet master 0–32768
2002–2017R/WSet channels 1–16, 0–32768
2018R/WApply: bit 15 set, bits 0–14 = zone
Values written to 200–203 are not saved and only take effect at boot; 207 = 260 saves them and reboots. Intensities are scaled 0–32768 for 0–100%; values above 32768 count as 100%.
Raw frame log