ICRI-IoT Modbus Sensor Board — Web Serial Client

Reads the holding registers an ICRI-IoT sensor board exposes when it runs in Modbus slave mode — RMS current of the six CT clamps, the two analog current and voltage inputs, up to 16 temperature probes and the power output states — directly from the browser, over Modbus RTU / Web Serial. Also sends the remote reboot command.

40 holding registers from address 0, read with function 0x03; function 0x06 writes the reboot command.

Web Serial API not available in this browser. Use a Chromium-based browser (Chrome, Edge, Opera) on desktop.

1. Connection

DISCONNECTED
Firmware defaults: address 1, 19200 baud, 8 data bits, no parity, 1 stop bit. The board only answers when its Modbus mode is set to Slave; address, baud rate and frame format are set from the board's own web configuration page (Settings → Serial). Connect the adapter's A and B lines to the board's RS485 terminals.

2. Live Readings

CT clamps — RMS current

InputRegValue

Analog inputs

InputRegValue

Power outputs & status

ItemRegValue

Temperature bus 1

ProbeReg°C

Temperature bus 2

ProbeReg°C

Temperature bus 3

ProbeReg°C

Temperature bus 4

ProbeReg°C
Currents and voltages are sent multiplied by 100 as signed 16-bit integers, so 1234 on the wire means 12.34. A temperature register reading 0x8000 means no probe is assigned to that slot, or the probe is disconnected or not responding. Which probe lands in which slot is set by the Modbus index assigned to each probe on the board's web page.
Reading History
Raw register dump
Reg Name Hex Unsigned Signed
Connect, then "Read Once" or start auto-polling.

3. Remote Reboot

Writes 1 to register 36 (rebt_c) with function 0x06. The board restarts within a fraction of a second and stops answering on the bus for a few seconds while it boots. Auto-polling is stopped first.
Register map
Register Name Content Scaling
0–5ac_c_1 … ac_c_6RMS current, CT clamps 1–6×100, A
6–7an_c_1, an_c_2Analog current inputs 1–2×100, mA
8–9an_v_1, an_v_2Analog voltage inputs 1–2×100, V
10–25te_1_1 … te_4_4Temperature, 4 buses × 4 probes×100, °C signed; 0x8000 = no reading
26–31—Unused—
32–33di_o_1, di_o_2Power output 1–2 state0 = off, 1 = on
34batt_vBattery voltagereserved
35wifi_cWiFi connected flagreserved
36rebt_cReboot commandwrite 1 to reboot
37err_coError counterreserved
38–39—Unused—
Registers marked reserved are part of the map but are not filled in by the current firmware, so they normally read 0.