Reads the holding registers an ICRI-IoT sensor board exposes when it runs in Modbus
slave mode — RMS current of the six CT clamps, the two analog current and voltage inputs,
up to 16 temperature probes and the power output states — directly from the browser, over Modbus RTU / Web
Serial. Also sends the remote reboot command.
40 holding registers from address 0, read with function 0x03; function 0x06 writes the reboot command.
Web Serial API not available in this browser. Use a Chromium-based browser
(Chrome, Edge, Opera) on desktop.
1. Connection
DISCONNECTED
Firmware defaults: address 1, 19200 baud, 8 data bits, no parity, 1 stop
bit. The board only answers when its Modbus mode is set to Slave; address, baud rate and
frame format are set from the board's own web configuration page (Settings → Serial). Connect the
adapter's A and B lines to the board's RS485 terminals.
2. Live Readings
CT clamps — RMS current
Input
Reg
Value
Analog inputs
Input
Reg
Value
Power outputs & status
Item
Reg
Value
Temperature bus 1
Probe
Reg
°C
Temperature bus 2
Probe
Reg
°C
Temperature bus 3
Probe
Reg
°C
Temperature bus 4
Probe
Reg
°C
Currents and voltages are sent multiplied by 100 as signed 16-bit integers, so 1234 on the wire means
12.34. A temperature register reading 0x8000 means no probe is assigned to that slot, or the probe
is disconnected or not responding. Which probe lands in which slot is set by the Modbus index assigned to each
probe on the board's web page.
Reading History
Raw register dump
Reg
Name
Hex
Unsigned
Signed
Connect, then "Read Once" or start auto-polling.
3. Remote Reboot
Writes 1 to register 36 (rebt_c) with function 0x06. The board restarts within a
fraction of a second and stops answering on the bus for a few seconds while it boots. Auto-polling is stopped
first.
Register map
Register
Name
Content
Scaling
0–5
ac_c_1 … ac_c_6
RMS current, CT clamps 1–6
×100, A
6–7
an_c_1, an_c_2
Analog current inputs 1–2
×100, mA
8–9
an_v_1, an_v_2
Analog voltage inputs 1–2
×100, V
10–25
te_1_1 … te_4_4
Temperature, 4 buses × 4 probes
×100, °C signed; 0x8000 = no reading
26–31
—
Unused
—
32–33
di_o_1, di_o_2
Power output 1–2 state
0 = off, 1 = on
34
batt_v
Battery voltage
reserved
35
wifi_c
WiFi connected flag
reserved
36
rebt_c
Reboot command
write 1 to reboot
37
err_co
Error counter
reserved
38–39
—
Unused
—
Registers marked reserved are part of the map but are not filled in by the current firmware, so they
normally read 0.